Designed and built to UL and FM fire pump requirements.
UL ListedFire pumpFM ApprovedFire pump
Features& design
All interior bolt or screw that are exposed to pumped liquid shall be of rolled bronze or corrosion resistant material. The pump shall be provided with automatic air-release valve, circulation relief valve and pressure gauges. Bearings shall have an L-10 rating of not less than 5000 hours at maximum load.
The pumps shall be provided with at least four packing rings plus a lantern ring.
The lantern ring may be permitted to replace one ring of packing.